Customized Products
Flame Retardant Multi-core Instrument Cable Comply to:IEC60332-3
6C×20AWG TC/ LSZH/ Wrapping/ OS/ FR LSZH
Application:
These cables are specially designed for requirements concerning the smoke density and acidic gas emitted in
case of fire. FIRETOX Cables are made with well chosen materials that not only can fulfill the conventional
requirements of Low Smoke Halogen Free, but also can reduce flame propagation in those instance where fire
may develop.
Construction:
Conductor:Stranded annealed tinned copper wires to BS 6360, class 2
Insulation:Low smoke,zero halogen (LSZH) insulated
Nominal thickness: 0.4 mm
Wrapping:Polyester tape
Screen:Overall Aluminium/Polyester tape applied with the metallic side down in electrical contact with a 0.5 mm²
tinned copper drain wire(7*0.31mm formation).
A 23 micron polyester tape is applied over the screening tape with a minimum 50% overlap.
Sheathing:Flame retardant LSZH with anti-termite and anti-rodent additive
Nominal thickness: 0.7mm
Overall diameter: 6.59+/-0.2mm
Packing: The cables are delivered on non-returnable wooden drums.
Standard IEC 60332-3
Physical characteristics:
Temperature rating: -40 to +90℃ Minimum bending radius
-for fixed wiring: 20mm
Flame retardant: IEC60332-3
Water resistant:IEC60529
Fire Retardancy Characteristics (For LSZH sheath):
Flame Propagation: IEC 332-1
Corrosive and Acid Gas Emission Test: Hydrochloric acid yield less than 0.5% in accordance with IEC 60754-1&2
Smoke Density:Percentage of light transmitted is greater than 60% when tested in accordance with IEC 61034-
1&2
Flammability:Temperature Index is around 250-280 deg when tested according to ISO 4589 or BS 2782 Part 1 Method 143A & 143
Electrical characteristics:
Rated voltage : 300/500V
Max conductor resistance at 20℃ : ≤33.8 Ohm/Km
Min insulation resistance : ≥100 M ohm/Km
Max inductance / resistance (L/R) ratio: 25 uH/ Ohm
Max. mutual capacitance at 1KHz:120 pF/m
Capacitance unbalance at 1khz:250 pF/ 250m
Test voltage:
core :core 1000V
core: screen 1000V